Specifications for TCU | Room Conditioning Units
Technical Specification
| TCU-4 | TCU-5 | |
|---|---|---|
| Panel Cut Out Size | 905x905mm |
4x 300mm dia holes (2x Outlet/2x Return) |
| Temperature Range | +5°C to +50°C | |
| Temperature Uniformity | +/- 2.0°C (Load Dependant) | |
| Humidity Range | 30% to 90% | |
| Humidity Uniformity | +/- 5% (Load Dependant) | |
| Heating Element Power | 1500 watts | 3x 1000 watts |
| Electrical | 15A/230V | 20A/415V/3Ph |
| Recommended Room Size | 20-30m3 | |
| Recommended Internal Room Height | 2300mm + (Plug is 250mm from ceiling) | |
| Recommended Coolroom Panel | 100mm Fire Rated PIR Panel | |
| Weight | 190kgs | 220kgs |
| Refrigerant Type | R507 | |
Features
| TCU-4 | TCU-5 | |
|---|---|---|
| STAR X Touch Screen | ✔ | ✔ |
| Ethernet Port | ✔ | ✔ |
| Download data to USB | ✔ | ✔ |
| Battery Backed-up Alarms | ✔ | ✔ |
| BMS | ✔ | ✔ |
| Supply Line Water Filters | 1x Carbon, 1x Sediment | 1x Carbon, 1x Sediment |
| Fibreglass Insulation | ✔ | ✔ |
Safety
| TCU-4 | TCU-5 | |
|---|---|---|
| Over Current Protection | ✔ | ✔ |
| Over Temperature Safety | ✔ | ✔ |
| Element Safety Cut Out | ✔ | ✔ |
Options
| TCU-4 | TCU-5 | |
|---|---|---|
| Ducting | Stainless steel ducting can be manufactured to suit your room | |
| CO2 Control | Set Point Control of CO2 Between Ambient and 3000ppm | |